Rack-mounted isolation-type inverter 10KW 48VDC/220VAC
1. Power Infrastructure and Energy Systems
Data Centers and Computer Rooms
: As a core component of UPS (Uninterruptible Power Supply) systems, it ensures continuous operation of servers and storage devices during utility power fluctuations or outages, preventing data loss. Its rack-mount design facilitates integration into standard 19-inch cabinets, saving space and simplifying maintenance.
Power Distribution Stations/Substations/Hydroelectric Power Plants
: Convert DC48V direct current to AC220V alternating current, powering monitoring systems, protective devices, and communication equipment. For instance, 10KW rack-mounted inverters are commonly used in distribution stations to ensure stable operation of electrical equipment.
New Energy Generation Systems
: In solar and wind power plants, convert DC electricity generated by photovoltaic panels/wind turbines into AC power to directly drive loads or provide stable power to energy storage systems. The high interference resistance of utility-frequency inverters adapts to complex outdoor electromagnetic environments.
2. Industrial and Transportation Sectors
Industrial Control and Equipment
: Provides stable AC power for industrial equipment such as machine tools, fans, pumps, variable frequency drives, and PLCs (Programmable Logic Controllers), supporting motor drives and automated production line operations. The strong load-bearing capacity of utility-frequency inverters handles inductive loads (e.g., motor start-up surges).
Transportation and Vehicle Systems
: Deployed in railways, ships, heavy trucks, and electric vehicles to supply reliable power to onboard equipment like communication systems, lighting, and air conditioning. For instance, rack-mounted inverters with DC inputs of 48V/96V/120V/240V/380V/480V/600V accommodate diverse vehicle power requirements.
|
Model |
BZP-10KW |
|||
|
Isolation mode |
Low Frequency Transformer |
|||
|
DC Input |
Rated voltage (Vdc) |
48V |
||
|
Rated current(A) |
208A |
|||
|
AC Output |
Rated output power |
10KW |
||
|
Output waveform |
Pure Sine Wave |
|||
|
Rated Voltage |
220V±3% |
380VAC±3% |
||
|
Phases |
Single phase |
3 phase 4 wire |
||
|
Rated current(A) |
45.5A |
15A (phase current) |
||
|
Frequency |
50Hz or 60Hz |
|||
|
Power Factor(PF) |
0.9 |
|||
|
Overload Ability |
150%, 5 seconds |
|||
|
Efficiency |
>88% |
|||
|
Waveform distortion rate (THD) |
<3%(Linear load) |
|||
|
Dynamic Response (0 to 100% load) |
5%,≤50ms |
|||
|
Display |
LCD |
|||
|
Running mode |
Working continuously |
|||
|
Electrical insulation properties |
2000Vac, 1 Minute |
|||
|
Communication interface (optional) |
RS485 |
|||
|
Protection Function |
Protection |
Input reverse polarity, under voltage, overvoltage, output over-current, short circuit, overheating etc. |
||
|
Cooling method |
Fan-cooled |
|||
|
Short-circuit protection |
No automatic recovery, need to restart the machine |
|||
|
Working environment |
Noise ( 1 meter) |
≤50dB |
||
|
Degree of protection |
IP20(indoor) |
|||
|
Working Altitude(m) |
≤2000 |
|||
|
Working temperature |
-25~+55℃ |
|||
|
relative humidity |
0~90%,non-condensing |
|||
|
Mechanical dimension |
Depth* Width * Height |
680x420x340mm |
||
|
Weight (Kg) |
150Kg |
155Kg |
||