China Economic AC/DC Battery Charger Suppliers - High Stability, Compact Design, Ideal for Industrial Applications
System Performance
Modular Architecture
Modular design with N+1 hot backup support, enabling smooth expansion and hot-swappable installation without system interruption.
Intelligent Automation
Achieves automatic module switch on/off, charging mode conversion, output voltage & current regulation, and SYNC switchover via serial communication.
Advanced Connectivity
Equipped with standard RS-485 and CAN interfaces, delivering seamless integration with industrial automation systems and full "4-remotes" capabilities.
Main Features
Product Parameters
| Parameter Item | Specification Details | |
|---|---|---|
| Model Item | 230D20NZ-D | |
| Output Current (A) | 20 | |
| Power (KW) | 6 | |
| Weight (kg) | 7.5 (with package) | |
| Cooling Type | Fan cooling | |
| Radiator T-rise | ≤30℃ | |
| Input Voltage (VAC) | Min | 323 |
| Typical | 380 | |
| Max | 437 | |
| Output Voltage (VDC) | Min | 176 |
| Typical | 242 | |
| Max | 300 | |
| Voltage Regulation | ±0.5% | |
| Current Regulation | ±1% | |
| Efficiency | ≥94% | |
| Storage Temperature (℃) | Min | -40 |
| Typical | 25 | |
| Max | 60 | |
| Working Temperature (℃) | Min | -10 |
| Typical | 25 | |
| Max | 40 | |
| Current Share Imbalance | ±3% | |
| Soft Start Time (S) | 3 ~ 8 | |
| Ripple | ≤0.5% | |
| Over Voltage Protection | 320 ± 15 VDC | |
| Automatic Current Limit | The output current does not increase infinitely. When overloaded, it switches to a limited constant current output, clamped to a maximum of 110% of rated output current. | |
| Load Grade | Continuous working with Grade I (100%) rating output current | |
| Short Circuit Protection | Self-protects against damage during short circuit; self-recoverable once fault is eliminated. | |
Frequently Asked Questions
The 230D20NZ-D delivers a rated output power of 6 kW with an adjustable output voltage range of 176 VDC to 300 VDC (typical 242 VDC) and a continuous output current of 20 A.
Yes. It features an N+1 hot backup modular design and advanced isolation automatic current sharing technology (imbalance < ±3%), supporting hot-swappable installation for easy expansion.
The module is built with standard RS-485 and CAN communication interfaces, fully supporting automation systems with "4-remotes" functionality (remote control, telemetry, remote signaling, and remote regulation).
In overload conditions, the module limits maximum output current to 110% of rated value in constant current mode. Under short circuit conditions, the module enters self-protection mode and automatically recovers once normal conditions return.
The module accepts a 3-phase AC input voltage ranging from 323 VAC to 437 VAC (typical 380 VAC), ensuring stable performance during utility grid fluctuations.
It utilizes built-in forced fan cooling, keeping the radiator temperature rise below ≤30℃ under continuous 100% Grade I load operation within a working temperature range of -10℃ to +40℃.